Analysis of the Reasons Why the Engine of a Diesel Generator Set Fails to Start Normally


Release time:

2025-09-28

There are many reasons why a diesel generator set engine fails to start. Most of the reasons are as follows:

There are many reasons why a diesel generator set engine fails to start. Most of the reasons are as follows:

​​No fuel in the fuel tank​​: The fuel tank is empty and needs to be refueled.

​​Solution​​: Fill the fuel tank with fuel.

​​Poor - quality fuel​​: The fuel quality is so poor that it cannot support the normal operation of the diesel engine.

​​Solution​​: Drain the fuel in the fuel tank, install a new fuel filter element, and add high - quality fuel to the fuel tank.

​​Dirty fuel filter​​: The fuel filter is too dirty.

​​Solution​​: Replace the fuel filter with a new one.

​​Broken or dirty fuel pipeline​​: The fuel pipeline is broken or dirty.

​​Solution​​: Clean or replace the fuel pipeline.

​​Low fuel pressure​​: The fuel pressure is too low.

​​Solution​​: Replace the fuel filter, check whether the fuel transfer pump is working properly. If necessary, install a new fuel transfer pump.

​​Air in the fuel system​​: There is air in the fuel system.

​​Solution​​: Find out the air - leaking parts in the fuel system and repair them. Remove the air from the fuel system.

​​Fixed drain valve in the open state​​: The fixed drain valve is in the open state (insufficient fuel pressure, unable to start the engine).

​​Solution​​: Replace the fixed drain valve.

​​Slow starting speed​​: The starting speed is slow.

​​Solution​​: Check the condition of the battery. If the battery is low - powered, charge the battery. If necessary, replace the battery.

​​Fuel supply solenoid valve fails to open normally​​: The fuel supply solenoid valve cannot open normally.

​​Solution​​: If the solenoid valve is damaged, replace it. Or check the circuit system and eliminate circuit faults. When starting with a 12V starting system, the starting voltage must not be lower than 10V. For a 24V system, the voltage must not be lower than 18V. If the voltage is lower than the minimum starting voltage, charge the battery or replace the battery.